Plant operating document: WaterPlant

Generated by PlantMind on 2026-10-28 03:22:53 from the approved PLC program. Synthetic plant, advisory document.

Overview (written by the model from the facts below)

LT-101 and LT-301 control P-101 start/stop; P-101 must be on for P-201 start and stop; P-201 also stops if AT-201 exceeds 1.8 or is commanded off via HMI; P-301 starts when LT-301 reaches 30.0 and stops when it falls below 20.0, with interlocks enforced during HMI commands.

Equipment and instruments

TagNameTypeUnit
LT-101Raw water tank levelsensor%
FT-101Intake flowsensorm3/h
AT-201Chlorine residualsensorppm
LT-301Treated water tank levelsensor%
PT-301Distribution discharge pressuresensorbar
P-101Intake pumppump-
P-201Chlorine dosing pumppump-
P-301Distribution pumppump-

Protective interlocks

IDProtectsTrips whenPurposeProgram
IL-01P-101LT-101 is below 15.0Trip intake pump on raw tank low-low (dry-run protection)line 53
IL-02P-101LT-301 is above 95.0Trip intake pump on treated tank high-high (overflow protection)line 55
IL-03P-201P-101 is offTrip chlorine dosing when there is no intake flowline 68
IL-04P-201AT-201 is above 4.0Trip chlorine dosing on chlorine overdoseline 70
IL-05P-301LT-301 is below 15.0Trip distribution pump on treated tank low-lowline 83
IL-06P-301PT-301 is above 6.0Trip distribution pump on overpressureline 85

What stops each pump

Automatic control

Alarms

IDWarns when
AL-01LT-101 is below 25.0
AL-02AT-201 is below 0.2
AL-03PT-301 is above 5.0

External command paths

Limits of this document